Self-Drilling Screws in Steel Studs for Signs: Pull-Out Data

Self-Drilling Screws in Steel Studs for Signs: Pull-Out Data

Self-drilling screws in steel studs get their pull-out capacity from the stud steel. In the ICC-ES reports for ITW Buildex and Hilti screws, the allowable pull-out of a screw increases with the design thickness of the stud, and the screw must pass through the stud with at least three threads past its back face. For a screw in tension, the design value is the least of pull-out, pullover and the screw’s own tension strength.

To find out if your sign needs a stamped design, read when you need an engineer for your sign project in Ontario.

What the code and the manuals require

The ICC-ES report ESR-1976 for ITW Buildex TEKS screws (reissued July 2025) and the ICC-ES report ESR-2196 for Hilti self-drilling screws (reissued October 2026) state that the screws comply with ASTM C1513. Both require engineered connections to comply with Section J4 of AISI S100.

Both reports use the US International Building Code. Their tables give allowable strength design (ASD) values with a factor of safety of 3.0. A design in Ontario uses limit states design to CSA S136. Do not use an ASD value as a factored resistance.

Published data: screw pull-out from steel studs

Pull-out depends on the member that is not in contact with the screw head. For a raceway screwed to a stud, that member is the stud. The table gives the allowable pull-out (ASD, Ω = 3.0) for steel with a minimum tensile strength (Fu) of 45 ksi.

Design thickness of the stud steel (in) #10-16 (lbf) #12-14, #12-24 (lbf) 1/4-14, 1/4-28 (lbf) Source
0.018 44 50 57 ESR-1976, July 2025, Table 2
0.030 73 83 96 ESR-1976, July 2025, Table 2
0.036 87 99 115 ESR-1976 Table 2; ESR-2196, October 2026, Table 2
0.048 116 132 153 ESR-1976 Table 2; ESR-2196 Table 2
0.060 145 165 191 ESR-1976 Table 2; ESR-2196 Table 2

The table footnotes add two rules:

  • Higher-strength steel. For Fu = 65 ksi, multiply by 1.44 (both reports). ESR-1976 gives 1.29 for Fu = 58 ksi.
  • Least value governs. In tension, use the least of pull-out (Table 2), pullover (Table 3) and fastener tension strength (Table 5).

The pull-out values match, and both reports calculate them to AISI S100. The screw’s own strength differs by product. Table 5 of each report gives these allowable tension values:

  • #10-16: 885 lbf for ITW Buildex TEKS, and 455 lbf for Hilti HWH, HHWH, PPH and PPCH screws.
  • #12-14: 1,184 lbf for ITW Buildex TEKS, and 775 lbf for Hilti HWH and TPCH screws.

Stud thickness: specify mils, not gauge

The Steel Network Light Steel Framing Members catalog (edition 022015, page 2) gives these design thicknesses:

  • 30 mil: 0.0312 in, gauge 20 (drywall).
  • 33 mil: 0.0346 in, gauge 20 (structural).
  • 43 mil: 0.0451 in, gauge 18.
  • 54 mil: 0.0566 in, gauge 16.

The catalog marks gauge numbers “reference only”. Its minimum delivered thickness is 95% of the design thickness. It lists structural Grade 33 steel at 45 ksi minimum tensile strength and Grade 50 steel at 65 ksi. It gives no tensile requirement for nonstructural ASTM A1003 NS33 steel.

A 33 mil stud (0.0346 in) is thinner than the 0.036 in column. The reports allow interpolation within the table (footnote 3).

How this applies to sign attachments

Both reports set conditions that matter for a raceway or backer box on a steel stud wall:

  • Three threads past the stud. The screw must pass through the supporting steel with at least three threads past its back side (Section 4.2 of both reports). ESR-1976 Table 1 gives a minimum protrusion of 0.425 in for a #10-16 TEKS/3 screw.
  • Drill point to suit the steel. ESR-1976 Table 1 gives a drilling capacity of 0.036 to 0.175 in of total steel for a #10-16 TEKS/3 screw. ESR-2196 Table 1 gives 0.110 to 0.175 in for a Hilti S-MD 10-16 HWH #3 point and 0.035 to 0.110 in for a #2 point.
  • Direct contact, steel to steel. The ESR-1976 values apply where the connected steel elements are in direct contact (Section 4.1.3). Both reports cover cold-formed steel members only (Section 2.0). The tables do not cover a raceway on sheathing, insulation or cladding, or an aluminum part under the screw head.
  • No increase for wind. The allowable values must not be increased for short-duration loads such as wind (ESR-1976 Section 5.4, ESR-2196 Section 5.2).
  • Combined loads. A sign screw can carry the sign weight in shear and wind suction in tension at the same time. Both reports put combined shear and tension outside their scope (Section 4.1.3).
  • Spacing and edge distance. Under the 2024 and 2021 IBC, both reports require a minimum spacing of 3 times the nominal screw diameter and a minimum edge distance of 1.5 times the diameter (Section 4.1.3).

What to show on sign permit drawings

The reports give screw data. They do not design the sign connection. The engineer designs it for each sign to Part 4 and CSA S136. Show these items on the sign permit drawings:

  • Studs. Size, spacing, thickness in mils and steel grade.
  • Screws. Manufacturer, product, size, length, drill point, coating and evaluation report number.
  • Build-up. Each layer between the raceway and the stud, and a screw length that gives three threads past the stud.
  • Backing. Blocking or backing plates where screws do not land on a stud.
  • Loads. The sign weight and the design loads to Part 4.

For a sign on EIFS over steel studs, read attaching signs to EIFS. For permit basics, read do I need a sign permit in Ontario. Our sign engineering service covers the attachment design and the stamped drawings.

Need help with sign engineering?

Send RHC the sign drawings, the sign weight, photos of the wall and any building drawings that show the stud size and thickness. Tell us the screw you plan to use. We reply within one business day. Contact us or read about our sign engineering services.

This article summarizes published manuals, evaluation reports and codes. It is not an engineering design. Check the current edition of each document. A licensed professional engineer must design and review the attachment for each sign.