Attaching signs to EIFS means that you fasten through the foam to blocking, framing or masonry behind it. You never anchor the sign in the foam. Sto states that its EIFS is not a base for sign anchors, and the Sto and Dryvit sign details put each bolt in a sealed sleeve.
RHC’s sign engineering is led by Irteza Ahmed, P.Eng., a former City of Toronto building plans examiner who reviewed sign permit applications.
In the Sto and Dryvit details, the EIFS layers include a water-resistive barrier, EPS insulation board, a base coat with embedded mesh, and a finish coat. This article summarizes what the code and the manufacturer documents say about a sign on these layers. To find out if your sign needs a stamped design, read when you need an engineer for your sign project in Ontario.
What the code and the manuals require
In Ontario, O. Reg. 163/24 on e-Laws adopts the National Building Code of Canada 2020, with the Ontario amendments, as the Building Code. The 2024 Building Code Compendium gives these rules:
- Signs. Division B, Article 3.15.3.1 requires all sign structures to be designed in accordance with Part 4.
- EIFS. Division B, Article 5.9.4.1 requires EIFS and their components to comply with Subsection 5.1.4, Sections 5.3 to 5.6 and CAN/ULC-S716.1.
- EIFS in Part 9 buildings. Article 9.27.14.3 requires design to CAN/ULC-S716.3 and installation to CAN/ULC-S716.2.
- Manufacturer literature. Note A-5.9.4.1.(1) refers designers to the EIFS Council of Canada’s EIFS Practice Manual and to the manufacturer’s literature.
Sto gives the structural rule in writing. The Sto StoTherm ci over Steel Frame Design Guide and Detail Booklet (Series 52s.xx, September 2025, page 6) states that StoTherm ci is non-structural and non-load bearing. It is not a base for the mechanical anchors of signs or light fixtures. The structural backup wall must be designed and built for these attachments to the applicable building code.
Published data: sign attachment details for EIFS
The values below are detail dimensions and product requirements. They are not load capacities. These documents come from the US offices of Sto Corp., Dryvit (Tremco CPG) and Sika. Confirm with the EIFS manufacturer that each detail applies to the system on your building.
| Item | Published value | Source |
|---|---|---|
| Perimeter sealant joint at all penetrations through StoTherm ci | 1/2 in (13 mm) wide, minimum | Sto Design Guide, Series 52s.xx, September 2025, page 8, note 5 |
| Space at a penetration through Outsulation LCMD, with sealant and closed-cell backer rod | 3/4 in (19 mm), minimum | Dryvit DS170, detail O-LCMD 37, 5/12/2023 |
| Space between the Dryvit finish face and the back of a sign | 1/2 in (12.7 mm), minimum | Dryvit DS170, detail O-LCMD 38, 5/12/2023 |
| Detail mesh wrapped to the back of the EPS at a penetration | 2 1/2 in (64 mm), minimum | Dryvit DS170, details O-LCMD 12 and 37, 5/12/2023 |
| StoGuard detail component on blocking at an electrical box, lapped onto the sheathing | 2 in, minimum | Sto detail 52s.73, September 2025 |
| Sealant for perimeter seals at wall penetrations | Low modulus; 50% elongation and 25% compression, minimum; ASTM C920, Grade NS | Sika Technical Bulletin, Acceptable Sealants, Rev April 2026 |
How this applies to sign attachments
The Sto sign attachment detail 52s.71 (September 2025) and the Dryvit Outsulation LCMD installation details, DS170 (detail O-LCMD 38, May 2023) show the same sequence:
- Find the structure behind the EIFS. Use framing, blocking, concrete or masonry. Do not use the foam.
- Install blocking where the bolt does not land on solid structure. Sto shows wood blocking in a steel stud wall. Dryvit shows blocking secured to the framing.
- Drill a hole through the EIFS and line it with sealant. Sto specifies a neutral-cure sealant.
- Install a sleeve in the hole. Sto shows a PVC or stainless steel sleeve that runs from the finish face through the blocking. Dryvit shows a non-corrosive pipe sleeve set in sealant.
- Bolt the sign through the sleeve to the blocking or framing. Sto shows a bolt with washers at each end. Dryvit shows a neoprene washer at the bolt head.
- Seal the joint behind the sign. Sto sets the washer behind the sign in sealant. Dryvit seals the perimeter of the sleeve to prevent water entry into the wall (note 2).
On a concrete masonry wall, Sto detail 52c.74 (October 2022) uses the same method for a surface-mounted fixture. It shows a PVC sleeve lined with sealant and a washer bedded in sealant.
An illuminated sign also needs a power feed through the wall. Sto detail 52s.73 (September 2025) mounts the exterior electrical box on blocking. The EPS is back-wrapped around the box, and a backer rod and sealant close the joint.
The sources also set these sealant rules:
- Bond to the base coat. Sto states that the sealant typically adheres to the reinforced base coat or the primed base coat (page 8). The Sika sealant bulletin tells installers not to apply sealant to the finish. Dryvit specifies Demandit or Color Prime on surfaces that receive sealant (O-LCMD 37).
- Use the correct backer rod. Sika calls for closed-cell or soft non-gassing backer rod and prohibits open-cell backer rod. Dryvit shows closed-cell backer rod.
- Prove compatibility. Sto asks for the sealant manufacturer’s certificate of compatibility and for field adhesion tests (page 8). Sika refers to field adhesion tests to ASTM C1521.
- Provide a joint. Sto requires joints at the perimeter of fixture attachments (page 9). Sika makes the design professional responsible for joint size, type and configuration.
What to show on sign permit drawings
The Sto and Dryvit details do not give fastener sizes, fastener loads or blocking sizes. The engineer designs these items for each sign, to Part 4. Show these items on the sign permit drawings for a sign on EIFS:
- Backup wall. Framing size and spacing, or the concrete or masonry type.
- Blocking. Material, size and connection to the framing.
- EIFS build-up. Each layer and the total thickness at the sign.
- Fasteners. Type, diameter, grade, length and embedment in the backup structure.
- Sleeve and seal. Sleeve material, washers, sealant, backer rod and the manufacturer detail number.
- Electrical penetration. The box location and its seal.
- Loads. The sign weight and the design loads to Division B, Article 3.15.3.1.
For permit basics, read do I need a sign permit in Ontario. Our sign engineering service covers the attachment design and the stamped drawings.
Need help with sign engineering?
Send RHC the sign drawings, the sign weight, photos of the wall and any building drawings that show the wall construction. Tell us the EIFS manufacturer if you know it. We reply within one business day. Contact us or read about our sign engineering services.
This article summarizes published manuals, evaluation reports and codes. It is not an engineering design. Check the current edition of each document. A licensed professional engineer must design and review the attachment for each sign.